Electrical Power Calculator

Work out the power a load uses, or the current it draws, for DC, single-phase (230 V in India) or three-phase (415 V) supplies.

Supply
Find
India: 230 V single phase, 415 V three phase (line to line).
1 for heaters and bulbs, about 0.8–0.9 for motors.
Results update as you type.

Real power

2.07 kW

2,070 W

Apparent power
2.3 kVA
Reactive power
1.00255 kVAR
Energy in 1 hour
2.07 units (kWh)
Horsepower
2.7759 hp

About this calculator

Power factor matters for motors, pumps and ACs; heaters and bulbs have a power factor of 1.

How to use it

  1. Choose the supply.
  2. Choose power or current.
  3. Enter the values.

The formula

Single phase: P = V × I × PF; three phase: P = √3 × V × I × PF
V
voltage (line to line for three phase)
I
current
PF
power factor

Worked example

A 7.5 kW three-phase motor at 415 V, PF 0.9

  1. I = 7,500 ÷ (1.732 × 415 × 0.9) = 11.6 A per line.

What the result means

kW is the real power you pay for; kVA is what the wiring and transformer must carry.

Assumptions

  • Balanced three-phase loads.

Limitations

  • Starting currents of motors are several times higher; size breakers with that in mind.

Frequently asked questions

How many amps is 1 kW at 230 V?

About 4.35 A at power factor 1.

What is power factor?

The ratio of real power (kW) to apparent power (kVA).

How do I convert kW to kVA?

Divide by the power factor.